Executive standard
Copper core and aluminum core XLPE insulated power cables with rated voltage of 35kV and below GB / t12706.2-2008, GB / t12706.3-2008, iec60502-1997
Product use
This product is applicable to the transmission and distribution of high-voltage power lines with rated voltage of 3 ~ 35kV.
Usage characteristics
1. The maximum rated temperature of the cable conductor shall be 90 ℃, and the maximum temperature of the cable conductor shall not exceed 250 ℃ in case of short circuit (the maximum duration shall not exceed 5S).
2. The ambient temperature during laying shall not be lower than 0 ℃. If it is lower than 0 ℃, it shall be preheated first.
3. Allowable bending radius during cable laying: single core cable shall not be less than 20 times of cable outer diameter; The multi-core cable shall not be less than 15 times the outer diameter of the cable.




















Hotline:86-13305254168
After sales:86-13808751185
Telephone:86-0514-84236288
Fax:86-0514-84237088
Addres:Lingtang Industrial Park, north suburb of Yangzhou
E-mail:cdjcable@163.com
Follow wechat
Mobile browsing
Copyright 2022 @Jiangsu changdejia Cable Co., Ltd